AC/DC Conversion (Rectification/Inversion):
Charging (AC → DC): When surplus energy is available from the grid or generated by a PV inverter, our advanced PCS (Power Conversion System) efficiently converts this AC power into DC electricity for battery storage. This essential process, known as rectification, ensures optimal energy utilization and storage.

,

Discharging (DC → AC): When power is required, the PCS transforms stored DC energy from the batteries back into AC power, delivering it to the grid or directly to electrical equipment. This conversion, referred to as inversion, facilitates seamless energy supply for residential or commercial needs.

,

Grid-Tied and Off-Grid Operation:
Designed for versatility, our PCS allows the energy storage system to seamlessly switch between grid-tied mode (connected to the grid) and off-grid mode (operating independently, such as in a microgrid). This feature is crucial for energy management in various applications, making our solutions ideal for China’s growing energy market.

,

As a leading supplier and factory of energy solutions, we prioritize high-quality manufacturing and innovative technology to meet the diverse needs of our customers.

,
  • Model Mars
  • Maximum DC voltage 1,000V
  • Minim um DC voltagel'1] 580V
  • DC voltage operating range 350-1000 V
  • Permissible grid voltage range 300-460 V
  • Rated grid frequency 50Hz/60Hz

Power Conversion Invertor Overview
🔋 Power Conversion Invertor

This is the core equipment in an energy storage system and is often referred to as the "brain" of the system. Its main function is to convert power between alternating current (AC) and direct current (DC), enabling the control and dispatch of electrical energy.

✔ Functions Include: AC/DC Conversion

Charging (AC → DC): When there is excess power from the grid (or AC power generated by a PV inverter), the PCS converts it into DC electricity to store in the batteries. This process is called rectification.

Discharging (DC → AC): When electricity is needed, the PCS converts the DC power from the batteries into AC power and supplies it to the grid or to the load (electrical equipment). This process is called inversion.

🔎 Grid-Tied and Off-Grid Operation

The PCS enables the energy storage system to switch between grid-tied mode (connected to the grid) and off-grid mode (operating independently, e.g., in a microgrid) as needed.

📶 EMS Smart Energy Management System
📷 Multiple configurable operating modes: off-grid, grid-tied, and grid charging
🖯 LCD smart touch Screen Display
🔉 AC/DC dual backup for auxiliary power supply
🔨 Control Technology for Unbalanced Loads
📨 Standard RS 485 modbus RTU protocol
📱 WIFI/ LAN Remote monitoring and control app available (optional)
🔌 Support add Static Transfer Switch (STS) for Grid-Tie/Off-Grid Applications (optional)
Model Mars-125KT Mars-110KT Mars-100KT
DC side parameters
Maximum DC voltage 1,000V 1,000 V 1,000v
Minimum DC voltage[1] 580V 580V 580V
DC voltage operating range 350-1000 V 350-1000V 350-1000v
Maximum DC current 216A 190A 173A
AC side parameters (grid-connected)
Rated charging/discharging power 125kW 110kW 100kw
Maximum charge and discharge power 150kW 132kW 120kw
Rated charge and discharge current 182A 160A 145A
Maximum charge-discharge current 217A 192A 174A
Rated grid voltage 400V 400V 400V
Permissible grid voltage range 300-460 V 300-460 V 300-460v
Rated grid frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz
Current total harmonic distortion rate <3% (at rated power) <3% (at rated power) <3% (at rated power)
Power factor > 0.99 > 0.99 >0.99
Power factor range -1~1 -1~1 -1~1
Overload capacity 1.2 Pn, continuous for 1 minute 1.2 Pn, continuous for 1 minute 1.2 Pn, continuous for 1 minute
AC side parameter (off-grid)
Rated input voltage 400V 400V 400V
Voltage deviation ±2% ±2% ±2%
etotalharonicdistortionrate <3% (linear load) <3% (linear load) <3% (linear load)
Efficiency
Maximum efficiency 98.9% 98.9% 98.9%
Protection
DC reverse polarity protection Supported Supported Supported
AC short-circuit protection Supported Supported Supported
AC output overcurrent protection Supported Supported Supported
Surge protection Level 2 Level 2 Level 2
Insulation resistance monitoring Supported Supported Supported
Temperature protection Supported Supported Supported
Basic parameters
Topology Without transformer Without transformer Without transformer
Ambient temperature -40℃~+60℃ -40℃~+60℃ -40℃~+60℃
Protection level IP20 (module and battery pack integrated solution, system protection level is IP54 or above) IP20 (module and battery pack integrated solution, system protection level is IP54 or above) IP20 (module and battery pack integrated solution, system protection level is IP54 or above)
PCS Product Structure
PCS Main Unit View
PCS Interface Details
Frequently Asked Questions (FAQ)

1. What is the primary function of the Power Conversion Inverter (PCS)?

The PCS acts as the "brain" of the energy storage system. Its main function is to convert power between alternating current (AC) and direct current (DC), managing both the charging process (AC to DC rectification) and the discharging process (DC to AC inversion) to control and dispatch electrical energy.

2. Can the Mars series PCS operate independently from the utility grid?

Yes. The Mars series PCS supports both grid-tied and off-grid operations. It enables the energy storage system to switch smoothly between grid-connected mode and independent off-grid mode (such as in a microgrid) as required by the site setup.

3. What communication and monitoring options are available?

The system features standard RS 485 Modbus RTU protocol interface. Additionally, users can opt for WIFI or LAN modules to enable remote monitoring and control via a dedicated application.

4. How does the system handle unbalanced loads?

The Mars PCS is equipped with advanced control technology specifically designed for unbalanced loads, ensuring stable and reliable power supply even when phase demands are unequal.

5. What safety protections are built into the Mars-100KT/110KT/125KT models?

The system includes comprehensive safety features such as DC reverse polarity protection, AC short-circuit protection, AC output overcurrent protection, Level 2 surge protection, insulation resistance monitoring, and automatic temperature protection.