| MODEL | AFVR-315 | AFVR-316 | AFVR-3110 | AFVR-3115 | AFVR-3120 | AFVR-3130 | AFVR-3150 | AFVR-31100 | AFVR-31200 | ||||||||
| Power Capacity(VA) | 5kVA | 6kVA | 10kVA | 15kVA | 20kVA | 30kVA | 50kVA | 100kVA | 200kVA | ||||||||
| Circuit Mode | IGBT/SPWM pulse width adjustment mode | ||||||||||||||||
| AC INPUT | Voltage | Standard 265V-495V(Or ±30% of Generator rated voltage) | |||||||||||||||
| Frequency | 30-100Hz | ||||||||||||||||
| Phase | Three Phase | ||||||||||||||||
| AC OUTPUT | Voltage | 110/120/220V±1% (customized) | |||||||||||||||
| Frequency | 50Hz/60Hz Adjustable | ||||||||||||||||
| Phase | Single Phase | ||||||||||||||||
| Frequency Stability | ≤±0.01% | ||||||||||||||||
| Voltage Stability | ≤1% | ||||||||||||||||
| Wave Distortion | ≤2% | ||||||||||||||||
| Reaction Time | ≤2mS | ||||||||||||||||
| Overload capacity | 110%,3 minutes, 200%,10 second | ||||||||||||||||
| Dynamic voltage transient range | 2%(0~100% load change) | ||||||||||||||||
| THDV | THD<3%(nonlinear load) | ||||||||||||||||
| DPI ( Dotsperinch ) | Display Window | High precision LCD touch screen display | |||||||||||||||
| Frequency Meter | 0.1Hz | ||||||||||||||||
| Voltage Meter | 0.1V | ||||||||||||||||
| Current Meter | 0. 1A | ||||||||||||||||
| Power Meter | 0.1W | ||||||||||||||||
| Efficiency | ≥90% suitable for inductive load, capacitive load, resistive load and any mixed load. | ||||||||||||||||
| Protection Function | The importation of non-fuse switch, without output fuse switch, the electronic circuit to detect over-voltage Express .Over voltage, over current, over temperature, over load, short circuit, and automatic alarm. | ||||||||||||||||
| Insulation Reactance | 500Vdc 20MΩ | ||||||||||||||||
| Pressure Endurance Insulation | 1500Vac/5mA/1min | ||||||||||||||||
| Cooling Model | Compulsive fan cooling | ||||||||||||||||
| Working Temperature | -10℃-45℃ IP22 | ||||||||||||||||
| Relative Humidity | 0-90%(No condensing) | ||||||||||||||||
| Altitude | 1500meters | ||||||||||||||||
| Dimension | Length (mm) | 350 | 350 | 400 | 400 | 500 | 500 | 650 | 650 | 1910 | |||||||
| Width (mm) | 560 | 560 | 660 | 660 | 830 | 830 | 1420 | 1420 | 1160 | ||||||||
| Height ( mm) | 600 | 600 | 700 | 700 | 1000 | 1000 | 1365 | 1365 | 1940 | ||||||||
| Net Weight(Kg) | 60kg | 65kg | 97kg | 107kg | 190kg | 215kg | 290kg | 460 | 850 | ||||||||
System Solution
Optional Function
Product Display
Frequently Asked Questions
Q1: What are the main advantages of the SPWM IGBT High-Frequency Inverter technology?
A1: This advanced technology provides a highly stable, pure sine wave output with high precision and efficiency (≥90%). It features an AC-DC-AC internal structure that isolates the output, protecting sensitive equipment from voltage fluctuations.
Q2: Can the output voltage and frequency be customized?
A2: Yes, the output voltage (such as 110V, 120V, or 220V with ±1% stability) and output frequency (50Hz/60Hz adjustable) can be customized to meet specific application requirements.
Q3: How does the remote monitoring system work?
A3: The system supports remote monitoring via RS485, WIFI, GPRS, or 2G/3G/4G/Ethernet. It allows real-time data viewing, historical curve tracking, and data downloads across PC, mobile apps, and WeChat platforms.
Q4: Is the AFVR series compatible with permanent magnet generators?
A4: Yes, the AFVR series is designed to work efficiently with permanent magnet generators, accommodating a wide input frequency range of 30-100Hz and wide input voltage variations.
Q5: What protective functions are built into these voltage regulators?
A5: It includes comprehensive protection mechanisms such as over-voltage, over-current, over-temperature, over-load, and short-circuit protection, complete with automatic alarms to ensure safe operation.
Q6: What load types can this system support?
A6: With an efficiency rating of ≥90%, the AFVR series is fully compatible with inductive loads, capacitive loads, resistive loads, and any mixed load configurations.